Need to know what size capacitor is required for your motor?
This table will guide you to find the correct size capacitor.
Recommended capacitor rating for direct connection induction motors to improve power factors to
0.95 or better at all loads. This table will help you calculate the required capacitor size relative to motor size.
Example: For a 10ph motor, with a motor speed of 750 RPM, the rated capacitor required will be 4mF.
Capacitor rating in kVAr when motor speed is:
Motor Power |
Motor Speed (RPM) |
kW |
hp |
3000 |
1500 |
1000 |
750 |
600 |
500 |
1.50 |
2 |
0.5 |
1 |
1 |
1.5 |
1.5 |
1.5 |
2.20 |
3 |
0.75 |
1 |
1 |
1.5 |
2 |
2 |
3.70 |
5 |
1 |
1.5 |
1.5 |
2.5 |
3 |
3 |
5.50 |
7.5 |
1.5 |
2 |
2.5 |
3 |
4 |
4 |
7.50 |
10 |
2.5 |
3 |
3 |
4 |
5 |
5 |
9 |
12 |
3 |
3 |
4 |
5 |
6 |
6 |
11 |
15 |
3 |
4 |
4 |
6 |
6 |
6 |
15 |
20 |
5 |
5 |
6 |
6 |
8 |
10 |
18.50 |
25 |
6 |
6 |
6 |
8 |
10 |
12 |
22.50 |
30 |
6 |
8 |
8 |
10 |
12 |
14 |
25 |
35 |
8 |
8 |
10 |
12 |
14 |
14 |
30 |
40 |
8 |
10 |
10 |
14 |
14 |
16 |
33 |
45 |
8 |
10 |
12 |
14 |
16 |
18 |
37 |
50 |
10 |
12 |
14 |
16 |
18 |
18 |
40 |
54 |
10 |
12 |
14 |
16 |
18 |
20 |
45 |
60 |
12 |
12 |
14 |
18 |
20 |
22 |
51 |
70 |
12 |
14 |
18 |
18 |
22 |
24 |
55 |
75 |
14 |
16 |
18 |
20 |
22 |
26 |
59 |
80 |
14 |
16 |
20 |
20 |
24 |
28 |
63 |
85 |
14 |
18 |
20 |
22 |
24 |
28 |
68 |
90 |
16 |
20 |
22 |
24 |
26 |
30 |
72 |
95 |
16 |
20 |
24 |
24 |
28 |
30 |
75 |
100 |
18 |
22 |
24 |
26 |
28 |
32 |
79 |
105 |
18 |
22 |
24 |
26 |
30 |
32 |
80 |
110 |
18 |
24 |
26 |
28 |
30 |
34 |
90 |
125 |
22 |
26 |
28 |
30 |
34 |
36 |
100 |
136 |
24 |
28 |
28 |
30 |
34 |
38 |
105 |
140 |
24 |
28 |
30 |
32 |
36 |
40 |
110 |
150 |
26 |
28 |
30 |
32 |
36 |
42 |
120 |
160 |
28 |
30 |
32 |
34 |
38 |
46 |
123 |
165 |
28 |
30 |
32 |
36 |
40 |
48 |
126 |
170 |
30 |
32 |
32 |
36 |
40 |
48 |
129 |
175 |
30 |
32 |
34 |
38 |
42 |
50 |
135 |
180 |
30 |
34 |
34 |
38 |
44 |
50 |
140 |
190 |
32 |
34 |
36 |
40 |
46 |
52 |
150 |
200 |
32 |
36 |
36 |
44 |
46 |
54 |